3 basic infeed, 1 basic infeed open-loop control – Efficient Networks Siemens Sinamics S120 User Manual

Page 38

Advertising
background image

Infeed

1.3 Basic Infeed

Drive Functions

38

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Signal name

Internal status

word

Parameter

PROFIdrive telegram 370

Pre-charging completed

ZSWAE.11

r0899.11

A_ZSW1.11

Line contactor energized feedback

ZSWAE.12

r0899.12

A_ZSW1.12

1.3

Basic Infeed

1.3.1

Basic Infeed open-loop control

General

Note
Line Modules (Active Line Modules, Basic Line Modules, Smart Line Modules) of different

types must not be operated simultaneously on the same DC link.

Features

● For Basic Line Modules Chassis and Booksize
● Unregulated DC link voltage
● Intregrated control of external braking resistors with 20 kW and 40 kW Basic Line

Modules (with temperature monitoring)

Description

Basic Infeed open-loop control can be used to switch on/off the Basic Line Module. The

Basic Line Module is an unregulated infeed unit without regenerative feedback capability.
The open-loop control firmware for the Basic Line Module runs on the Control Unit assigned

to it. The Basic Line Module and Control Unit communicate via DRIVE-CLiQ.