Efficient Networks Siemens Sinamics S120 User Manual

Page 386

Advertising
background image

Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

386

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Bit

Meaning

Remarks

BICO

1

Digital input/output 9

(DI/DO 9)

– DI/DO 9 on the Control Unit must be parameterized as an output

(p0728.9 = 1).

BI: p0739

2

Digital input/output 10

(DI/DO 10)

– DI/DO 10 on the Control Unit must be parameterized as an output

(p0728.10 = 1).

BI: p0740

3

Digital input/output 11

(DI/DO 11)

– DI/DO 11 on the Control Unit must be parameterized as an output

(p0728.11 = 1).

BI: p0741

4

Digital input/output 12

(DI/DO 12)

– DI/DO 12 on the Control Unit must be parameterized as an output

(p0728.12 = 1).

BI: p0742

5

Digital input/output 13

(DI/DO 13)

– DI/DO 13 on the Control Unit must be parameterized as an output

(p0728.13 = 1).

BI: p0743

6

Digital input/output 14

(DI/DO 14)

– DI/DO 14 on the Control Unit must be parameterized as an output

(p0728.14 = 1).

BI: p0744

7

Digital input/output 15

(DI/DO 15)

– DI/DO 15 on the Control Unit must be parameterized as an output

(p0728.15 = 1).

BI: p0745

8...

15

Reserved

– –

Note:

The bidirectional digital inputs/outputs (DI/DO) can be connected as either an input or an output (see also transmit signal

E_DIGITAL).

MT_STW

Control word for the "central probe" function. Display via r0685.

Table 10-23 Description of MT_STW (control word for Control Unit)

Bit

Meaning

Remarks

BICO

0

Falling edge probe 1

1

Falling edge probe 2

2

Falling edge probe 3

3

Falling edge probe 4

4

Falling edge probe 5

5

Falling edge probe 6

Activation of measuring time determination with the next falling

edge
For telegram 392, in addition, probes 3 and 6

6...7 Reserved

– –

8

Rising edge probe 1

9

Rising edge probe 2

10 Rising edge probe 3

11 Rising edge probe 4

12 Rising edge probe 5

13 Rising edge probe 6

Activation of measuring time determination with the next rising edge
For telegram 392, in addition, probes 3 and 6

14...

15

Reserved

– –

CI: p0682

CU_ZSW (status word for Control Unit, CU)

See function diagram [2458]

Advertising