Infeed

1.2 Smart Infeed

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

37

Note
Under the condition that the drive system was commissioned with STARTER and no

PROFIdrive telegram was activated, the infeed can be powered-up by issuing an enable

signal at the EP terminals and a positive signal edge at OFF1 (p0840).

Switching off the Smart Line Module

To switch off the Active Line Module, carry out the steps for switching it on in reverse order.
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.

This allows the attached drives to be braked in a controlled manner.

Control and status messages

Table 1-5

Smart Infeed open-loop control

Signal name

Internal control word

Binector input

Display of internal

control word

PROFIdrive telegram 370

ON/OFF1

STWAE.0

p0840 ON/OFF1

r0898.0

A_STW1.0

OFF2

STWAE.1

p0844 1 OFF2 and

p0845 2 OFF2

r0898.1

A_STW1.1

Enable operation

STWAE.3

p0852 Enable

operation

r0898.3

A_STW1.3

Inhibit regenerating

STWAE.6

p3533 Inhibit

regenerating

r0898.6

A_STW1.6

Acknowledge error

STWAE.7

p2103 1 Acknowledge

or

p2104 2 Acknowledge

or

p2105 3 Acknowledge

r2138.7

A_STW1.7

Master ctrl by PLC

STWAE.10

p0854 Master ctrl by

PLC

r0898.10

A_STW1.10

Table 1-6

Smart Infeed status message

Signal name

Internal status

word

Parameter

PROFIdrive telegram 370

Ready to power up

ZSWAE.0

r0899.0

A_ZSW1.0

Ready to run

ZSWAE.1

r0899.1

A_ZSW1.1

Operation enabled

ZSWAE.2

r0899.2

A_ZSW1.2

Fault active

ZSWAE.3

r2139.3

A_ZSW1.3

No OFF2 active

ZSWAE.4

r0899.4

A_ZSW1.4

Power-on disable

ZSWAE.6

r0899.6

A_ZSW1.6

Alarm present

ZSWAE.7

r2139.7

A_ZSW1.7

Master ctrl by PLC

ZSWAE.9

r0899.9

A_ZSW1.9