Basic functions

6.8 Armature short-circuit brake, internal voltage protection, DC brake

Drive Functions

192

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

External armature short-circuit braking

The external armature short-circuit is activated via p1231 = 1 (with contactor feedback

signal) or p1231 = 2 (without contactor feedback signal). It is initiated when the pulses are

canceled.
This function controls an external contactor via output terminals, which then short-circuits the

motor through resistors when the pulses are canceled. Armature short-circuit braking has the

advantage with respect to a mechanical brake that at the start of braking (at a high speed),

the braking effect is initially high. However, at lower speeds, the braking effect is significantly

decreases - this is the reason that we recommend a combination with a mechanical brake.
A prerequisite for the use of the external armature short-circuit is:
● One of the following motor types was parameterized:

– Rotating permanent-magnet synchronous motor (p0300 = 2xx)
– Linear permanent-magnet synchronous motor (p0300 = 4xx)

In case of incorrect parameterization (e.g. induction motor and external armature short-circuit

selected), an error 7906 "Armature short-circuit / DC brake parameterization error" is

generated.

&RQWDFWRUIHHGEDFN

&RQWDFWRU2Q

'ULYHVWDWXV666>@

+:SXOVHHQDEOH

3XOVHLQKLELW

&RQWDFWRUIHHGEDFN2SHQPLVVLQJ

&RQWDFWRUIHHGEDFN&ORVHGPLVVLQJ

+:SXOVHHQDEOH

&RQYHUWHU

&RQWURO8QLW

$6&DFW

~

M

3

p1236 = 200 ms

=1

T

0

+24 V

0

T

p1237 = 200 ms

&

&

1

(r0046.19 = 1)

1

r0046.4

r0046.20

≥1

DI

p1231 = 1

r0002 = 19

2000 µs

DO

p1235

r1239.0

p1231 = 2

p1231 = 1

(0)

p1230

A07904

F07905

Figure 6-3

External armature short-circuit braking with/without contactor feedback signal

Internal voltage protection (booksize)

The internal voltage protection is activated with p1231 = 3. It is initiated when the pulses are

canceled.
The internal voltage protection is used to protect the drive group when the pulses are

cancelled. This is realized by short-circuiting a half bridge in the power unit (Motor Module).