Vector control

4.3 Speed controller

Drive Functions

120

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

RQO\DFWLYHLISUHFRQWUROLVDFWLYH
S!

6SHHGDFWXDOYDOXH

6SHHGVHWSRLQW

6SHHG

FRQWURO

3UH

FRQWURO

3,

6SHHG

FRQWUROOHU

7RUTXH

VHWSRLQW

'URRS

LQMHFWLRQ



9&







L

7

S

.

Q

7

L

7

S

.

Q

7

U>@

U

U>@

U

S

S

S

U

U

U

U

U
U

S

S

S

6/9&

Figure 4-4

Speed controller

The optimum speed controller setting can be determined via the automatic speed controller

optimization function (p1900 = 1, rotating measurement).
If the inertia load has been specified, the speed controller (Kp, Tn) can be calculated by

means of automatic parameterization (p0340 = 4). The controller parameters are defined in

accordance with the symmetrical optimum as follows:
Tn = 4 * Ts
Kp = 0.5 * r0345 / Ts = 2 * r0345 / Tn
Ts = total of the short delay times (contains p1442 and p1452)
If vibrations occur with these settings, the speed controller gain Kp must be reduced

manually. Actual-speed-value smoothing can also be increased (standard procedure for

gearless or high-frequency torsion vibrations) and the controller calculation performed again

because this value is also used to calculate Kp and Tn.
The following relationships apply for optimization:
● If Kp is increased, the controller becomes faster, although overshoot is reduced. Signal

ripples and vibrations in the speed control loop, however, increase.

● If Tn is decreased, the controller still becomes faster, although overshoot is increased.
When speed control is set manually, it is easiest to define the possible dynamic response via

Kp (and actual speed value smoothing) first before reducing the integral time as much as

possible. When doing so, closed-loop control must also remain stable in the field-weakening

range.
To suppress any vibrations that occur in the speed controller, it is usually only necessary to

increase the smoothing time in p1452 for operation with an encoder or p1442 for operation

without an encoder or reduce the controller gain.
The integral output of the speed controller can be monitored via r1482 and the limited

controller output via r1508 (torque setpoint).