3.14 Vdc control

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

105

feed energy back, the drives with an active Vdc_max controller can even be accelerated to

absorb the braking energy and, in turn, relieve the DC link.

Description of Vdc_max control without acceleration (p1240 = 7, 9)

As with p1240 = 1, 3, if the drive must not be accelerated by means of feedback from other

drives in the DC link, acceleration can be prevented by the setting p1240 = 7, 9. The

effective lower torque limit must not be greater than the torque limit offset (p1532).

Description of Vdc controller monitoring functions (p1240 = 4, 5, 6)

In the event of a power failure, the Line Module can no longer supply the DC link voltage,

particularly if the Motor Modules in the DC link line-up are drawing active power. To ensure

that the DC link voltage is not burdened with uncritical drives in the event of a power failure,

these drives can be switched off by a fault (F30003) with a parameterizable voltage

threshold (p1248). This is carried out by activating the Vdc_min monitoring function (p1240 =

5, 6).
In the event of a power failure, the DC link voltage can increase until it reaches the shutdown

threshold when drives are decelerated. To ensure that the DC link voltage is not burdened

with uncritical drives in the event of a power failure, these drives can be switched off by a

fault (F30002) with a parameterizable voltage threshold (p1244). This is carried out by

activating the Vdc_max monitoring function (p1240 = 4, 6).

Function diagrams (see SINAMICS S List Manual)

● 5650 Vdc_max controller and Vdc_min controller

Overview of key parameters (see SINAMICS S List Manual)

Adjustable parameters

● p1240 Vdc controller or Vdc monitoring configuration
● p1244 DC link voltage threshold, upper
● p1248 DC link voltage threshold, lower
● p1250 Vdc controller proportional gain

Display parameters

● r0056.14 Vdc_max controller active
● r0056.15 Vdc_min controller active