Infeed

1.4 Line contactor control

Drive Functions

42

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Control and status messages

Table 1-7

Basic Infeed open-loop control

Signal name

Internal control word

Binector input

Display of internal

control word

PROFIdrive telegram

370

ON/OFF1

STWAE.0

p0840 ON/OFF1

r0898.0

A_STW1.0

OFF2

STWAE.1

p0844 1 OFF2 and

p0845 2 OFF2

r0898.1

A_STW1.1

Acknowledge error

STWAE.7

p2103 1 Acknowledge

or

p2104 2 Acknowledge

or

p2105 3 Acknowledge

r2138.7

A_STW1.7

Master ctrl by PLC

STWAE.10

p0854 Master ctrl by

PLC

r0898.10

A_STW1.10

Table 1-8

Basic Infeed status message

Signal name

Internal status word

Parameter

PROFIdrive telegram 370

Ready to power up

ZSWAE.0

r0899.0

A_ZSW1.0

Ready to run

ZSWAE.1

r0899.1

A_ZSW1.1

Operation enabled

ZSWAE.2

r0899.2

A_ZSW1.2

No OFF2 active

ZSWAE.4

r0899.4

A_ZSW1.4

Power-on disable

ZSWAE.6

r0899.6

A_ZSW1.6

Master ctrl by PLC

ZSWAE.9

r0899.9

A_ZSW1.9

Pre-charging completed

ZSWAE.11

r0899.11

A_ZSW1.11

Line contactor energized

feedback

ZSWAE.12

r0899.12

A_ZSW1.12

1.4

Line contactor control

Description

This function can be used to control an external line contactor. Opening and closing the line

contactor can be monitored by evaluating the feedback contact in the line contactor. The line

contactor is used for the electrical isolation of the DC link for the energy supply network.
The line contactor can be controlled using the following drive objects:
● Via bit r0863.1 of drive object INFEED
● Via bit r0863.1 of drive object SERVO/VECTOR

Note
For more information on the line connection, see the Equipment Manuals.