Safety Integrated basic functions

9.8 Acceptance test and certificate

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

331

No.

Description

Status

r9773.0 = r9773.1 = 0 (STO de-selected and inactive – drive)

r9773.2 = 1 (SS1 active – drive)

STO is initiated after the SS1 delay time expires (p9652, p9852).

No safety faults and alarms (r0945, r2122, r2132)

r9722.0 = r9772.1 = 1 (STO selected and active – CU)

r9872.0 = r9872.1 = 1 (STO selected and active – MM)

r9772.2 = r9872.2 = 0 (SS1 inactive – CU and MM)

r9773.0 = r9773.1 = 1 (STO selected and active – drive)

r9773.2 = 0 (SS1 inactive – drive)

6.

Deselect SS1

Check the following:

No safety faults and alarms (r0945, r2122, r2132)

r9722.0 = r9772.1 = 0 (STO de-selected and inactive - CU)

r9872.0 = r9872.1 = 0 (STO de-selected and inactive – MM)

r9772.2 = r9872.2 = 0 (SS1 inactive – CU and MM)

r9773.0 = r9773.1 = 1 (STO selected and active – drive)

r9773.2 = 0 (SS1 inactive – drive)

7.

r0046.0 = 1 (drive in "Power-on inhibit" state)

8.

Acknowledge "Power-on inhibit" and run the drive

Ensure that the correct drive is running

9.

The following is tested:

Correct parameterization of the SS1 function

9.8.5

Acceptance test for "Safe Brake Control" (SBC)

"Safe Brake Control" function (SBC)

This test comprises the following steps:

Table 9-12 "Safe brake control" (SBC) function

No.

Description

Status

Initial state

Drive in "Ready" status (p0010 = 0)

STO function enabled (p9601.0 = 1, p9801.0 = 1)

Enable SBC function (p9602 = 1, p9802 = 1)

1.

Vertical axis:
Brake as in sequential control (p1215 = 1)

No vertical axis:
Brake always released (p1215 = 2)