Procedure for star/delta switchover – Efficient Networks Siemens Sinamics S120 User Manual

Page 458

Advertising
background image

Applications

11.3 Motor changeover

Drive Functions

458

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

U
U
U

S>@

.+

.
.

.

.

8
9

:

8
9

:

.

.

.

.

.+

.+

.+

S>@

Figure 11-3 Example: star/delta switchover

Table 11-4 Settings for the example

Parameter

Settings

Comments

p0130

2

Configure 2 MDS.

p0180

2

Configure 2 DDS.

p0186[0..1]

0, 1

The MDS are assigned to the DDS.

p0820

p2197.2

p0821 to p0824 0

0

Switchover to delta connection after speed in

p2155 is exceeded.

p0826[0..1]

0; 0

Identical numbers signify the same thermal

model.

p0827[0..1]

1, 2

Assign the bit from p0830 to the MDS. If

p0827[0] = 1, for example, bit p0830.1 is set when

MDS0 is selected via DDS0.

p0830.1 and p0830.2

Digital outputs auxiliary

contactors

The digital outputs for the auxiliary contactors are

assigned to the bits.

p0831[0..1]

Digital inputs auxiliary

contacts

The digital inputs for the checkback from the

motor contactors are assigned.

p0833.0..2

0, 0, 0

The drive is responsible for controlling the

contactor circuit and the pulse inhibit. Parking bit

(Gn_ZSW14) is set.

p2155

Switchover speed

Sets the speed at which the switchover is to be

carried out in delta.

Procedure for star/delta switchover

1. Start condition:

For synchronous motors, the actual speed must be lower than the star field weakening

speed. This prevents the regenerative voltage from exceeding the terminal voltage.

2. Pulse inhibit:

After selecting a new drive data set using p0820, the pulses are inhibited.