Off responses, Vector control 4.7 torque control – Efficient Networks Siemens Sinamics S120 User Manual

Page 130

Advertising
background image

Vector control

4.7 Torque control

Drive Functions

130

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

6SHHGVHWSRLQW

3,

VSHHG

FRQWUROOHU

7RUTXH
VHWSRLQW

6SHHGDFWXDOYDOXH

0BVHW

0BVXSSO

 0BUHJDFWLYH

S 0

5HJ

0BVXSSO

0BVXSSOVFDO

0BVXSSOVFDO

S>'@ 

-

r1547[0]

r1538

r1547[1]

r1539

T

i

K

p

T

n

r0079

1

(0)

p1512[C]

(0)

p1513[C]

(0)

p1511[C]

(0)

p1503[C]

r1406.12

[FP2520.7]

p1501

r1515

r1407.2

0

1

Figure 4-11 Closed-loop speed/torque control

The total of the two torque setpoints is limited in the same way as the speed control torque

setpoint. Above the maximum speed (p1082), a speed limiting controller reduces the torque

limits in order to prevent the drive from accelerating any further.
True torque control (with self-adjusting speed) is only possible in closed-loop but not open-

loop control for sensorless vector control (SLVC). In open-loop control, the torque setpoint

adjusts the setpoint speed via a ramp function generator (integration time ~ p1499 x p0341 x

p0342). For this reason, sensorless torque control at standstill is only suitable for

applications that require an accelerating torque but no load torque (e.g. traction drives). This

restriction does not apply to torque control with sensor.

OFF responses

● OFF1 and p1300 = 22, 23

– Reaction as for OFF2

● OFF1, p1501 = "1" signal and p1300 ≠ 22, 23

– No separate braking response; the braking response takes place by a drive that

specifies the torque.

– The pulses are suppressed when the brake application time (p1217) expires. Standstill

is detected when the actual speed value is less than the speed threshold (p1226) or

when the monitoring time (p1227) that started when speed setpoint ≤ speed threshold

(p1226) has expired.

– Power-on disable is activated.

Advertising