Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

291

Monitoring and protective functions

8

8.1

Power unit protection, general

Description

SINAMICS power units offer comprehensive functions for protecting power components.

Table 8-1

General protection for power units

Protection against:

Precautions

Responses

Monitoring with two thresholds:

First threshold exceeded


A30031, A30032, A30033

Current limiting of a phase has responded.

The pulsing in the phase involved is inhibited.

If it is too frequently exceeded

F30017 –> OFF2

Overcurrent

1)

Second threshold exceeded

F30001 "Overcurrent" –> OFF2

Overvoltage

1)

Comparison of DC link voltage with

hardware shutdown threshold

F30002 "Overvoltage" –> OFF2

Undervoltage

1)

Comparison of DC link voltage with

hardware shutdown threshold

F30003 "Undervoltage" –> OFF2

Second monitoring threshold checked

for overcurrent

F30001 "Overcurrent" –> OFF2

Short-circuit

1)

Uce monitoring of IGBT modules

(chassis only)

F30022 "Uce monitoring" –> OFF2 (chassis only)

Ground fault

Monitoring the sum of all phase currents

After threshold in p0287 is exceeded:

F30021 "Power unit: ground fault"

--> OFF2
Note:

The sum of all phase currents is displayed in

r0069[6]. For operation, the value in p0287[1]

must be greater than the sum of the phase

currents when the insulation is intact.

Line phase failure

detection

1)

F30011 "Line phase-failure in main circuit" –>

OFF2

1) The monitoring thresholds are permanently defined in the converter and cannot be changed.