Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

385

Receive signals:

● CU_STW Control Unit control word
● A_DIGITAL digital outputs
● MT_STW probe control word

Transmit signals:

● CU_ZSW Control Unit status word
● E_DIGITAL digital inputs
● MT_CTW Probe status word
● MTn_ZS_F Probe n measuring time, falling edge (n = 1, 2)
● MTn_ZS_S Probe n measuring time, rising edge (n = 1, 2)

CU_STW (control word for Control Unit, CU)

See function diagram [2448]

Table 10-21 Description of CU_STW (control word for Control Unit, CU)

Bit

Meaning

Remarks

BICO

0

Synchronization flag

This signal is used to synchronize the joint system time between the

controller and drive unit.

BI: p0681[0]

1

RTC PING

This signal is used to set the UTC time using the PING event.

BI: p3104

2...6 Reserved

7

Acknowledging faults

0/1

Acknowledging faults

BI: p2103

8...11 Reserved

12 Controller sign-of-life

bit 0

13 Controller sign-of-life

bit 1

14 Controller sign-of-life

bit 2

15 Controller sign-of-life

bit 3

Controller sign-of-life

CI: p2045

A_DIGITAL (digital outputs)

This process data can be used to control the Control Unit outputs.

See function diagram [2449]

Table 10-22 Description of A_DIGITAL (digital outputs)

Bit

Meaning

Remarks

BICO

0

Digital input/output 8

(DI/DO 8)

– DI/DO 8 on the Control Unit must be parameterized as an output

(p0728.8 = 1).

BI: p0738