Infeed

1.2 Smart Infeed

Drive Functions

34

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Note
If the line supply environment changes, or the components connected to the DClink (e.g.

after installing and mounting the equipment at the customer's site or after expanding the

drive group), then the line supply/DC link identification routine should be repeated with

p3410 = 5. Only then can it be guaranteed that the infeed operates with an optimum

controller setting.
When the identification function is activated, alarm A06400 is output.

CAUTION

The line supply and DC link identification routine is not permissible for Smart Line Modules

of the Chassis type.

Identification methods

For additional identification methods, see the SINAMICS S List Manual.
● p3410 = 4: An identification run for the total inductance and DC link capacitance is

initiated when the pulses are next enabled (two measuring routines with different current

magnitudes). Data determined during identification (r3411 and r3412) is entered into

p3421 and p3422 and the controller is recalculated. At the same time, the parameters for

current controller adaptation are determined (p6320, p6322). All of the parameters for the

Infeed Module are then automatically stored in a non-volatile memory.
The infeed continues to operate without any interruption with the new controller

parameters.

● p3410 = 5: The same measurements and write operations are always carried-out for

p3410 = 4. However, before the first identification run, the parameter values for line

inductance and DC link capacitance are reset (p3421 = p0223 and p3422 = p0227) and

the coarse settings are made for the controller.
p3410 is automatically set to 0 after an identification run has been successfully

completed.

Note
Identification using p3410 = 5 should preferably be used.

It may be necessary to reset the closed-loop controller to the factory settings if an

identification run was unsuccessful, for example.

Overview of key parameters (SINAMICS S List Manual)

● p3410 Infeed identification method
● p3421 Infeed inductance
● p3422 Infeed DC link capacity