Efficient Networks Siemens Sinamics S120 User Manual

Page 176

Advertising
background image

Vector V/f control (r0108.2 = 0)

5.4 Vdc control

Drive Functions

176

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Reduce the regenerative torque to maintain the DC link voltage within permissible

limits.

● Undervoltage in the DC link

– Typical cause

Failure of the supply voltage or supply for the DC link.

– Remedy

Specify a regenerative torque for the rotating drive to compensate the existing losses,

thereby stabilizing the voltage in the DC link (kinetic buffering).

Properties

● Vdc control

– This comprises Vdc_max control and Vdc_min control (kinetic buffering), which are

independent of each other.

– Joint PI controllers. The dynamic factor is used to set Vdc_min and Vdc_max control

to a smoother or harder setting independently of each other.

● Vdc_min control (kinetic buffering)

– With this function, the kinetic energy of the motor is used for buffering the DC link

voltage in the event of a momentary power failure, thereby delaying the drive.

● Vdc_max control

– This function can be used to control momentary regenerative load without shutdown

with “overvoltage in the DC link“.

– Vdc_max control is only recommended with a supply without active closed-loop control

for the DC link and without feedback.

Description of Vdc_min control

9

GF

FWUODFWLYH

ZLWKRXWSRZHUUHVWRUHIDXOW)

3RZHUUHVWRUH

ZLWKRXW.,3IDXOW)

3RZHUIDLOXUH

7

3RZHUIDLOXUH

Q

VHWS

PLQ

9




U

W

W

W

Figure 5-7

Switching Vdc_min control on/off (kinetic buffering)