background image

Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions

418

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Name

Value

1)

Limit value

Description

T

DX

+ T

O_MIN

≤ T

O

≤ T

DP

Time of setpoint transfer

This is the time at which the transferred setpoints (speed

setpoint) are accepted by the closed-loop control system after

the start of the cycle.
T

O

= integer multiple of T

BASE_IO

Servo calculation: T

O

= 4 ∙ T

BASE_IO

= 500 µs

When T

O

= 0: T

O

≐ T

DP

Vector calculation: T

O

= 4 ∙ 1000 µs = 4000 µs

When T

O

= 0: T

O

≐ T

DP

T

O

corresponds to the largest speed controller cycle (p0115[1])

of a drive object (vector) in the drive unit.

T

O

4

T

O_MIN

= 1

Servo:

Minimum time distance between T

O

and T

DX

T

O_MIN

= 1 ∙ T

BASE_IO

= 125 µs

Vector:

Minimum time distance between T

O

and T

DX

T

O_MIN

= 1 ∙ T

n_reg

= 1000 µs

T

n_reg

corresponds to the largest speed controller cycle

(p0115[1]) of a drive object (vector) in the drive unit.

T

DX

E10 hex

3600 dec

T

DX

< T

DP

Data exchange time

This is the time required within one cycle for transferring

process data to all available slaves.
T

DX

= integer multiple of T

Bit

T

Bit

= 1/12 µs at 12 MBaud

calculation: T

DX

= 3600 • T

BIT

= 300 µs

T

PLL_W

0

-

PLL window

(half the width of the GC synchronization window)
The following applies to the setting:

Small window --> minimization of synchronization

fluctuations on the drive

Large window --> higher tolerance of GC fluctuations

Calculation (assumption: T

PLL_W

= A hex ≐ 10 dez)

T

PLL_W

= 10 • TBIT = 0.833 µs

T

Bit

= 1/12 µs at 12 Mbps

T

PLL_D

0

-

PLL dead time

The PLL dead time can be used to compensate for different

data transfer times to the slaves (e.g. due to repeaters).
The slaves with faster transfer times are delayed by a

corresponding PLL dead time.
Calculation: T

PLL_D

= 0 ∙ T

BIT

= 0 µs

T

Bit

= 1/12 µs at 12 MBaud

GC

Global Control Telegram (Broadcast Telegram)

T

TH

Token hold time

This time is calculated by the engineering system.

Dx

Data_Exchange

This service is used to implement user data exchange between

master and slave 1 - n.