Safety Integrated basic functions

9.7 Commissioning the "STO", "SBC" and "SS1" functions

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

323

No.

Parameter

Description/comments

12 p0010 = Value not

equal to 95

Safety Integrated: exit commissioning mode

If at least one safety monitoring function is enabled (p9601 = p9801 ≠ 0), the

checksums are checked:
If the target checksum on the Control Unit has not been correctly adapted, then fault

F01650 (SI CU: Acceptance test required) is output with fault code 2000 and it is not

possible to exit the safety commissioning mode.
If the target checksum on Motor Modules has not been correctly adapted, then fault

F01650 (SI CU: Acceptance test required) is output with fault code 2001 and it is not

possible to exit the safety commissioning mode.

If a safety monitoring function has not been enabled (p9601 = p9801 = 0), safety

commissioning mode is exited without the checksums being checked.

When safety commissioning mode is exited, the following is carried out:

The new safety parameters are active on the Control Unit and Motor Module.

13

All drive parameters (entire drive group or only single axis) must be manually saved from

RAM to ROM. These data are not saved automatically!

14 POWER ON

Carry-out a POWER ON.
After commissioning, a POWER ON reset must be carried out.

15 -

Carry out acceptance test and create test certificate.
Once safety commissioning is complete, the commissioning engineer must carry out an

acceptance test for the enabled safety monitoring functions.
The results of the acceptance test must be documented in an acceptance certificate.

9.7.3

Safety faults

Stop response

When Safety Integrated faults occur, the following stop responses can be triggered:

Table 9-5

Safety Integrated stop responses

Stop response

Action

Effect

Triggered ...

STOP A cannot be

acknowledged

For all non-

acknowledgeable

Safety faults with pulse

disable.

STOP A

Trigger safe pulse

suppression via the switch-

off signal path for the

relevant monitoring channel.
During operation with SBC:

apply motor holding brake.

The motor coasts to a

standstill or is braked

by the holding brake.

For all

acknowledgeable

safety faults with pulse

disable.
As a follow-up reaction

of STOP F.