Basic information about the drive system

12.4 BICO technology: interconnecting signals

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

483

Fixed values for interconnection using BICO technology

The following connector outputs are available for interconnecting any fixed value settings:
● p2900[0...n] CO: Fixed value_%_1
● p2901[0...n] CO: Fixed value_%_2
● p2930[0...n] CO: Fixed value_M_1
Example:
These parameters can be used to interconnect the scaling factor for the main setpoint or to

interconnect an additional torque.

12.4.7

Scaling

Signals for the analog outputs

Table 12-5 List of signals for analog outputs

Signal

Parameter

Unit

Normalization

(100 % = ...)

Speed setpoint before the setpoint

filter

r0060

RPM

p2000

Speed actual value motor encoder

r0061

RPM

p2000

Actual speed

r0063

RPM

p2000

Drive output frequency

r0066

Hz

Reference frequency

Absolute current actual value

r0068

Aeff

p2002

Actual DC link voltage value

r0070

V

p2001

Total torque setpoint

r0079

Nm

p2003

Actual active power

r0082

kW

r2004

Control deviation

r0064

RPM

p2000

Modulation depth

r0074

%

Reference control factor

Current setpoint, torque-generating

r0077

A

p2002

Current actual value, torque-

generating

r0078

A

p2002

Flux setpoint

r0083

%

Reference flux

Flux actual value

r0084

%

Reference flux

Speed controller

PI torque output

r1480

Nm

p2003

Speed controller

I torque output

r1482

Nm

p2003