3 connections of the sk ti4-tu-msw – NORD Drivesystems BU0200 User Manual

Page 103

Advertising
background image

SK 200E Manual for frequency inverters

102

Subject to technical alterations

BU 0200 GB-4411

3.5.1.3

Connections of the SK TI4-TU-MSW

Connection of the incoming and outgoing mains cable (incl. PE) is made on the relevant terminal blocks as
shown in the illustration. With single phase mains cables the conducting phase must be connected to L1
and the neutral conductor to L2.

Control connection details

NOTE

The use of SK TU4-MSW / SK TI4-TU-MSW on SK 2xxE, size 4 is not permitted!

The maintenance switch is only approved for frequency inverters of size 1 to 3 (230V / 4kW
or 400V / 7.5kW) and compliance with the maximum rated current (16A).

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

Supply (Mains input)

L1

Mains connection

1st phase

I

nom

= 16A

Mains connection, according to
network
1~100 - 240V to L1 and L2

or

3~ 200 - 500V to L1, L2 and L3

-

L2

Mains connection

2nd phase or "N"

-

L3

Mains connection

3rd phase

-

PE

PE, Earth

-

Output

L1

Mains connection

1st phase

I

nom

= 16A

Frequency inverter connection,
according to network
1~100 - 240V to L1 and L2

or

3~ 200 - 500V to L1, L2 and L3

-

L2

Mains connection

2nd phase or "N"

-

L3

Mains connection

3rd phase

-

PE

PE, Earth

-

Connection to the terminal bar

of the SK TI4-TU-MSW

Supply (mains)

Output (frequency inverter)