8 Technical data

8.1 General data for frequency inverter series SK 2xxE

Function

Specification

Output frequency

0.0 … 400.0Hz

Pulse frequency

3.0 … 16.0kHz, standard setting = 6kHz
Power reduction > 8kHz for 115/230V device, >6kHz for 400V device.

Typical overload capacity

150% for 60s, 200% for 3.5s

Protective measures against

Overtemperature of the frequency inverter,
overvoltage and undervoltage

Short-circuit, earthing fault,
overload, idling

Regulation and control

Sensorless current vector control (ISD), linear V/f characteristic curve,
automatic flux adaptation (energy-saving function)

Motor temperature monitoring

I

2

t motor, PTC / Bimetal switch

Digital input

3 or 4x, Low 0-5V, High 14-30V, R

i

= 9.5k

, C

i

= 10nF, cycle time = 4ms

Electrical isolation

Control terminals

Control outputs

Digital output:

Brake rectifier:

18-30V DC (according to VI 24V), max. 200mA, max. 100k

load

max. 0.5A choke current, voltage according to mains

Interfaces

Standard: RS 485 (USS)

RS 232 (Single Slave)
System bus

Option: Profibus, CANopen,

DeviceNet, AS-Interface,
EtherCAT, PROFINET

Efficiency of frequency inverter

approx. 95% according to size

Storage and transport temperature

-

25°C … +60 / 70°C

Operating / ambient temperature

-

25°C … +50°C, according to operating mode (Details: Section 8.3)

ATEX: -

20…+40°C (Details: Section 2.10)

Long-term storage

See Section 9.12.1

Protection class

IP55, optionally IP66 (S 4 only IP55 without or with IP66 special measures
according to Section 1.7)

Max. Installation altitude above sea
level

Up to 1000m:

No power reduction

1000...4000m:

1%/ 100m power reduction (up to 2000m overvoltage cat. 3)

2000...4000m:

Only overvoltage category 2 is complied with, external
overvoltage protection at the mains input is necessary

Ambient conditions

Transport (IEC 60721-3-2):

Vibration: 2M2

Operation (IEC 60721-3-3):

Vibration: 3M7;

Climate: 3K3 (IP55) / 3K4 (IP66)

Waiting period between
two power-up cycles

60 sec for all devices in normal operating cycle

Connection
terminals

Mains/motor/brake
resistance

4mm

2

flexible with wiring sleeves, 6mm

2

with rigid cable

Terminal screw
tightening
torque
1.2...1.5Nm

Control unit /System bus 2.5mm

2

, with wiring sleeves 1.5mm

2

RS485 / RS232

1x RJ12 (6-pin)

SK 2x0E:

24V - Output
(Terminal 43)

24V DC ±25%, max. 200mA

Digital outputs

24V DC ±25%, max. 20mA

SK 2x5E:

24V supply - input
(Terminal 44)

18…30V DC, at least 200...800mA according to load

Digital output

18…30V DC, according to supply voltage (Terminal 44) , max. 200mA

Advertising