SK 200E Manual for frequency inverters

210

Subject to technical alterations

BU 0200 GB-4411

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P483

[-01]

...

...

[-10]

Hyst. BusIO Out Bits

(Hysteresis of bus I/O Out bits)

S

1 … 100 %

{ all 10 }

Difference between switch-on and switch-off point to prevent oscillation of the output signal.

[-01] = Bus / AS-i Dig Out1

(Bus IO Out Bit 0 + AS-i 1)

[-02] = Bus / AS-i Dig Out2

(Bus IO Out Bit 1 + AS-i 2)

[-03] = Bus / AS-i Dig Out3

(Bus IO Out Bit 2 + AS-i 3)

[-04] = Bus / AS-i Dig Out4

(Bus IO Out Bit 3 + AS-i 4)

[-05] = Bus / IOE Dig In1

(Bus IO In Bit 4 + DO 1 of the first SK xU4-IOE (DigOut 02))

[-06] = Bus / IOE Dig Out2

(Bus IO In Bit 5 + DO 2 of the first SK xU4-IOE (DigOut 03))

[-07] = Bus / 2nd IOE Dig Out1

(Flag 1 + DO 1 of the second SK xU4-IOE (DigOut 04))

[-08] = Bus / 2nd IOE Dig Out2

(Flag 2 + DO 2 of the second SK xU4-IOE (DigOut 05))

[-09] = Bit 10 BUS status word

[-10] = Bit 13 BUS status word

NOTE:

Details for the use of the bus systems can be found in the relevant supplementary bus manual.