3 signal status leds – NORD Drivesystems BU0200 User Manual

Page 86

Advertising
background image

3 Options

BU 0200 GB-4411

Subject to technical alterations

85

3.4.3.3

Signal status LEDs

The statuses shown by the LED can be read out with the aid of a parameterisation tool from Getriebebau
NORD (NORD CON software, SimpleBox, ParameterBox) and of course via the information parameter
(P173) "Module Status" (Section 6.3.2).

Displays specific to the module
The status of the Technology Unit or the system bus is indicated by the LEDs DS and DE.

LED (green)

DS

Device State

LED (red)

DE

Device Error

Meaning

... slow flashing = 2Hz (0.5s cycle)

… quick flashing = 4Hz (0.25s cycle)

OFF

OFF

Technology Unit not ready, no control voltage

ON

OFF

Technology Unit ready, no error, at least one frequency inverter is
communicating via the system bus

ON

Flashing 0.25s

Technology Unit ready, however

one or more of the connected frequency inverters
is in error status

Flashing 0.25s OFF

Technology Unit ready and at least one further participant is connected
to the system bus, however,

 there is no frequency inverter on the system bus (or the connection
is interrupted)

 Address error of one or more system bus participants

Flashing 0.25s Flashing 0.25s

Flashing interval
1 x - 1s pause

System bus is in "Bus Warning" status

 Communication on the system bus faulty or

 no other participant on the system bus

Flashing 0.25s Flashing 0.25s

Flashing interval
2 x - 1s pause

 System bus is in "Bus Off" status or

 the 24V voltage supply to the system bus
has been interrupted during operation

Flashing 0.25s Flashing 0.25s

Flashing interval
3 x - 1s pause

 no 24V voltage supply to the system bus
(System bus is in "Bus Off" status)

Flashing 0.25s Flashing 0.25s

Flashing interval
4 x - 1s pause

Module fault

 EEPROM fault

Flashing 0.25s Flashing 0.25s

Flashing interval
5 x - 1s pause

Module fault

 AOUT error (analog output)

 DIP switch configuration error

OFF

Flashing 0.25s

Flashing

interval

1…7 - 1s pause

System error, internal program execution fault

 EMC interference (observe wiring guidelines!)

 Module faulty