SK 200E Manual for frequency inverters

222

Subject to technical alterations

BU 0200 GB-4411

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P540

Mode phase sequence

(Rotation direction mode)

S

P

0 ... 7

{ 0 }

For safety reasons this parameter can be used to prevent a rotation direction reversal and
therefore the incorrect rotation direction.
This function does not operate if the position control is active (P600 ≠ 0).

0 = No limitation, "No restriction of direction of rotation"

1 = Disable phase seq key, "Disable phase sequence key", rotation direction change key

of the SimpleBox is locked

2 = To the right only*, only right-hand field rotation direction is possible. The selection of

the "incorrect" rotation direction leads to the output of the minimum frequency P104
with the field of rotation R.

3 = To the left only*, only a left-hand field rotation direction is possible. The selection of the

"incorrect" rotation direction leads to the output of the minimum frequency P104 with
the field of rotation L.

4 = Enabl direct only, "Enable direction only", rotation direction is only possible according

to the enable signal, otherwise 0Hz is output.

5 = Right Orient. Contr. "Only right-hand running monitored" *, only a right-hand field

rotation is possible. The selection of the "incorrect" rotation direction leads to a switch-
off (control lock) of the FI. If necessary, care should be taken that the setpoint (>f

min

) is

sufficiently high.

6 = Left Orient. Contr. "Only left-hand running monitored" *, only a left field rotation is

possible. The selection of the "incorrect" rotation direction leads to a switch-off (control
lock) of the FI. If necessary, care should be taken that the setpoint (>f

min

) is sufficiently

high.

7 = Enab direct contr, "Only enabled direction controlled", rotation direction is only

possible according to the enable signal, otherwise the FI is switched off.


*) Applies for control via keyboard and control terminals.