1 electrical data 1~115v – NORD Drivesystems BU0200 User Manual

Page 274

Advertising
background image

8 Technical data

BU 0200 GB-4411

Subject to technical alterations

273

8.3.1

Electrical data 1~115V

Size 1

Size 2

Device type:

SK 2x5E…

-250-112-O

-370-112-O

-550-112-O

-750-112-O

Nominal motor power

(4-pole standard motor)

230V

0.25 kW

0.37 kW

0.55 kW

0.75 kW

240V

1

/

3

hp

½ hp

¾ hp

1 hp

In

p

u

t

Mains voltage

1~ 115V

1 AC

110 … 120V,

10%, 47 … 63Hz

Typical input current
at 115V

1~ rms

8.9 A

11 A

13.1 A

20.1 A

1~ FLA

8.9 A

10.8 A

13.1 A

20.1 A

Rec. mains fuse

1 AC

slow-acting [A]

16 A

16 A

16 A

25 A

Permissible
mains fuses (UL)

RK5 or faster

fuses, min. 115V

30 A

30 A

30 A

30 A

Bussmann

FRS-R-30

FRS-R-30

FRS-R-30

FRS-R-30

Circuit breaker*

min. 115V

25 A

25 A

25 A

25 A

O

u

tp

u

t

Output voltage

3~ 230V

3 AC 0

– 2x mains voltage

Nominal output
current at 230V

rms

1.7 A

2.2 A

3.0 A

4.0 A

Motor

Assembly**

1.7 A

1.7 A

3.0 A

3.0 A

Wall-mounted**

1.7 A

2.2 A

3.0 A

4.0 A

Min. braking resistor

75

75

75

75

Recommended braking
resistor

Section 2.3

100

100

100

100

Motor-mounted (ventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.25kW / 1.6A

0.25kW / 1.7A

0.25kW / 1.7A

0.25kW / 1.6A

0.25kW / 1.8A

0.37kW / 2.0A

0.37kW / 2.6A

0.55kW / 3.0A

0.55kW / 3.0A

0.37kW / 2.6A

0.55kW / 3.0A

0.55kW / 3.4A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

47°C

50°C

50°C

23°C

35°C

30°C

40°C

50°C

45°C

11°C

25°C

20°C

Wall mounting (ventilated / unventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.25kW / 1.6A

0.25kW / 1.7A

0.25kW / 1.7A

0.25kW / 1.6A

0.37kW / 2.0A

0.37kW / 2.1A

0.55kW / 3.0A

0.55kW / 3.0A

0.55kW / 3.0A

0.55kW / 3.0A

0.55kW / 3.3A

0.55kW / 3.6A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

48°C

50°C

50°C

36°C

40°C

40°C

50°C

50°C

50°C

16°C

30°C

25°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)

Advertising