3 Options

BU 0200 GB-4411

Subject to technical alterations

97

Control connection details

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

44

24V

24V supply

24VDC ±25%

20mA

Connection of the supply voltage
for the module and the reference
potential of the analog signals

112 AGND/0V

Reference potential
for analogue signals

111 10V REF

+10V
Reference voltage

+10V, 5mA

Connection of reference voltage
from frequency inverter

114

AIN1

Analog input 1

U= -

10 … +10V, R

i

=2MΩ

Resolution 10Bit

Signal IN

Signal OUT

Terminal

Value Terminal

Value

114

-10V

117

+10V

114

+10V

117

0V

116

-10V

118

+10V

116

+10V

118

0V

The conversion of the analog
signals is inverted.

Assignment of the functions of the
analog input signals is made via
parameter P400[...] of the
frequency inverter.

116

AIN2

Analog input 2

117

AOUT1

Analog output 1

Resolution: 10Bit
Precision: 0.25V

Load capacity with signal:
0…10V: ≤ 10mA

118

AOUT2

Analog output 2

Potential isolation

C1

DIN1

Digital input 1

Relay input:
Low: 0-5V (2.8kOhm)
High: 18-30V (1.6kOhm)

Reaction time max. 7ms

Assignment of the functions of the
analog output signals is made via
parameter P434[...] of the
frequency inverter.

C2

DIN2

Digital input 2

40 GND /0V

Reference potential
for digital signals

R14

R1 NO

Relay 1.1
Normally closed
contact

Relay input:
Low: 0-5V (2.8kOhm)
High: 18-30V (1.6kOhm)

Reaction time max. 7ms

Mechanical

lifetime:
1x10

8

(1 billion) OPS

(Operations)

Electrical:
3x10

5

(3 million) OPS

(Operations)

Relay (changeover) with function:

Closer:

R11 / R14

Opener:

R11 / R12

R12

R1 NC

Relay 1.2
Normally opened
contact

R11

Relay 1.3
Common contact

R24

R2 NO

Relay 2.1
Normally closed
contact

Relay (changeover) with function:

Closer:

R21 / R24

Opener:

R21 / R22

R22

R2 NC

Relay 2.2
Normally opened
contact

R21

Relay 2.3
Common contact