6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

203

Value Function

Description

Signal

45

3-W-Ctrl. Start-Right

“3-Wire-Control Start-Right”

(Closing button)

This control function provides an alternative to enable R/L (01/ 02),
in which a permanently applied level is required.

Here, only a control impulse is required to trigger the function. The
control of the FI can therefore be performed entirely with buttons.

0

1

Flank

46

3-W-Ctrl Start-Left

“3-Wire-Control Start-Left”

(Closing button)

0

1

Flank

49

3-Wire-Ctrl. Stop

“3-Wire-Control Stop”

(Opening button)

10

Flank

47

Motorpot. Freq.

+

"

Motor potentiometer frequency +"

In combination with enable R/L the output frequency can be
continuously varied. To save a current value in P113, both inputs
must be at a High voltage for 0.5s. This value then applies as the
next starting value for the same direction of rotation (Enable R/L)
otherwise start at f

MIN

.

High

48

Motorpot. Freq.

-

"

Motor potentiometer frequency -"

High

50

Bit 0 Fixed frequency array

Binary coded digital inputs to generate up to 15 fixed frequencies.
(P465: [-01] ... [-15])

High

51

Bit 1 Fixed frequency array

High

52

Bit 2 Fixed frequency array

High

53

Bit 3 Fixed frequency array

High

55

… 64 reserved for Posicon BU 0210

65

2

Man/auto release brake

"Release brake manually/
automatically"

The brake is automatically released by the frequency inverter
(automatic brake control) if this digital input has been set.

High

66

2

Man. release brake

"Release brake manually"

The brake is only released of the digital input is set.

High

67

Dig.out. man/auto set

"Set digital output manually /
automatically"

Set digital output 1 manually, or via the function set in (P434)

High

68

Dig.out. man. set

"Set digital output manually"

Set digital output 1 manually

High

69

Speed meas. with ini.

"Speed measurement with
initiator"

Simple speed measurement (impulse measurement) with initiator

Impulses

70

Evacuation run

"Activate evacuation run"

This also provides the possibility of operation with a very low link
circuit voltage (e.g. using batteries). With this function the charging
relay is activated and the undervoltage and phase error detection
are deactivated.

ATTENTION! There is no overload monitoring! (e.g. lifting gear)

High

71

Motorpot.F+ and Save

"Motor potentiometer function

Frequency + with automatic
saving"

With this motor potentiometer function, a setpoint value is set and
saved via the digital inputs. With control enabling R/L this is then
started up in the correspondingly enabled direction. On change of
direction the frequency is retained.
Simultaneous activation of the +/- function causes the frequency
setpoint value to be set to zero.
The frequency setpoint value can also be displayed or set in the
operating value display (P001=30, current setpoint MP-S) or in P718.
Any minimum frequency set (P104) is still effective. Other setpoint
values, e.g. analog or fixed frequencies can be added or subtracted.
The adjustment of the frequency setpoint value is performed with
the ramps from P102/103.

High

72

Motorpot.F- and Save

"Motor potentiometer function

Frequency - with automatic
saving"

High

73 ²

Inhibit right+ Quick

"Inhibit turn right+ Quick Stop"

As for setting 31, but coupled to the "Quick Stop" function.

Low

74 ²

Inhibit left+ Quick

"Inhibit turn left+ Quick Stop"

As for setting 32, but coupled to the "Quick Stop" function.

Low

...continued on the next page