SK 200E Manual for frequency inverters

276

Subject to technical alterations

BU 0200 GB-4411

Size 2

Size 3

Device type:

SK 2xxE…

-151-323-A

-221-323-A

-301-323-A

-401-323-A

Nominal motor power

(4-pole standard motor)

230V

1.5 kW

2.2 kW

3.0 kW

4.0 kW

240V

2 hp

3 hp

4 hp

5 hp

In

p

u

t

Mains voltage

3~ 230V

3 AC 200 ... 240V,

10%, 47 ... 63 Hz

Typical input current
at 230V

3~ rms

6.6 A

9.1 A

11.8 A

15.1 A

3~ FLA

6.6 A

9.1 A

11.7 A

14.9 A

Rec. mains fuse

1 AC

slow-acting [A]

16 A

20 A

20 A

25 A

Permissible
mains fuses (UL)

RK5 or faster

fuses, min. 230V

10 A

30 A

30 A

30 A

Bussmann

FRS-R-10

FRS-R-30

FRS-R-30

FRS-R-30

Circuit breaker*

min. 230V

10 A

25 A

25 A

25 A

O

u

tp

u

t

Output voltage

3~ 230V

3 AC 0 - Mains voltage

Nominal output
current at 230V

rms

7.0 A

9.5 A

12.5 A

16.0 A

Motor

Assembly**

7.0A

(45°C)

9.5A

(45°C)

12.5A

(45°C)

16.0A

(45°C)

Wall-mounted**

5.5 A

5.5 A

8.0 A

8.0A

Min. braking resistor

62

62

33

33

Recommended braking
resistor

Section 2.3

200

200

100

100

Motor-mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (or -2) (ventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

1.10kW / 7.0A

1.10kW / 7.0A

1.10kW / 9.2A

2.20kW / 9.5A

3.0kW / 12.5A

3.0kW / 12.5A

3.0kW / 14.5A

4.0kW / 16.0A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

49°C

50°C

50°C

50°C

50°C

50°C

46°C

47°C

47°C

Wall mounting (unventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.55kW / 3.8A

0.75kW / 4.8A

1.10kW / 5.7A

0.75kW / 4.7A

1.10kW / 5.8A

1.10kW / 6.7A

1.1kW / 6.8A

1.5kW / 8.7A

2.2kW / 10.4A

1.1kW / 6.8A

1.5kW / 8.7A

2.2kW / 10.4A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

15°C

25°C

20°C

6°C

20°C

10°C

18°C

30°C

25°C

-4°C

0°C

0°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)