3 Options

BU 0200 GB-4411

Subject to technical alterations

89

Details of the control connections

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

44

24V

24V supply

(module, field and
system bus level)

24VDC ±20%

≈ 90mA
protected against reverse
polarity

Max. permissible current
load: 2A

Connection for module supply
voltage and 24V source for the
digital inputs (DIN1 and DIN2)

-

40

GND/0V

Reference potential
for digital signals

-

C1

DIN1

Digital input 1

(I/O PROFIBUS DP DIN1)

Low 0V ... 5V

High 15V ... 30V

R

i

= 8.1k

Input capacitance 10nF

Scan rate 1 ms

Each digital input has a reaction
time of 1ms

Inputs compliant with
EN 61131-2,

Type 1

P174

C2

DIN2

Digital input 2

(I/O PROFIBUS DP DIN2)

P174

77

Sys H

System bus
data cable +

System bus
interface

-

78

Sys L

System bus
data cable -

-

40

GND/0V

Reference potential
for digital signals

24VDC ±20%

≈ 90mA
protected against reverse
polarity

Max. permissible current
load: 2A

Connection for module supply
voltage and source for the digital
inputs
(DIN1 and DIN2)

-

44

24V

24V supply

(module, field and
system bus level)

-

Potential separation

82

PBR B

(incoming)

Bus +
(red wire)

RxD/TxD-P

RS485 transfer
technology

The use of a twisted, shielded two-
wire cable / Profibus cable type A
is strongly recommended

-

81

PBR A

(incoming)

Bus -
(green wire)

RxD/TxD-N

-

46

GND/

0V BUS

Data ground Bus

-

83

RTS

Ready to send

-

47

VO/

5V BUS

5V bus supply
voltage

internal Profibus voltage
supply

Note: Should not be used
externally!

-

82

PBR B

(outgoing)

Bus
(red wire)

RxD/TxD-P

RS485 transfer
technology

The use of a twisted, shielded two-
wire cable / Profibus cable type A
is strongly recommended

-

81

PBR A

(outgoing)

Bus
(green wire)

RxD/TxD-N

-

46

GND/

0V BUS

Data ground Bus

-