SK 200E Manual for frequency inverters

78

Subject to technical alterations

BU 0200 GB-4411

Details of the control connections

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

44

24V

24V supply

24VDC ±10%

max. 420mA (total)

integrated
short-circuit monitoring,
limited overtemperature
and overload monitoring

Supply voltage (output) to supply
an SK 2x5E or other module with
24V.

Can also be used as an input (in
this case, do not connect L1 and
L2), if the module is only to be
used as a voltage or frequency
converter (for the connection of a
potentiometer).

-

40

GND/0V

GND
Reference potential

-

44

24V

24V supply

-

40

GND/0V

GND
Reference potential

-

11

10V REF

+10V
reference voltage

10V ± 0.2V

Max.
load 5mA

For connection of potentiometer
5 -

10kΩ.

A

500Ω burden resistor for the

evaluation of 0/4 - 20mA signals is
contained in the enclosed bag.

-

14

AIN1+

Analog input 1

positive

0 … 10V,
Resolution: 8Bit
Accuracy: 0,2V

-

12 AGND/0V

Analog Ground

Reference potential for
analog signals

-

B1

DOUT

FOUT
Frequency output

SPS compatible in
compliance with
EN61131-2
Low: 0V, High: 24V
Pulse frequency:
~ 1 - 32kHz

Impulses for evaluation via the
digital input function P420 [02]/[03]
= 26/27 and the analog meaning in
P400 [-06]/[-07].

P420

P400

40

GND/0V

GND
Reference potential

-

Potential separation

L1

Mains connection

1. Phase

Mains connection, 100 - 240V or
380 - 500V, depending on the
module

-

L2

Mains connection

2. Phase

-

PE

PE, Earth

As required, does not need to be
connected.

-

PE

PE, Earth

-