6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

221

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P536

Current limit

(Current limit)

S

0.1 ... 2.0 / 2.1
(x FI current rating)

{ 1.5 }

The inverter output current is limited to the set value. If this limit value is reached, the inverter
reduces the actual output frequency.

With the analog input function in P400 = 12/13, this limit value can also be varied and cause an
error message (E12.4).

0.1 ... 2.0 = Multiplier with the inverter current rating, gives the limit value

2.1 = OFF means that this limit value is disabled. The FI supplies the maximum possible

current.

P537

Pulse disconnection

(Pulse disconnection)

S

10 ... 200 % / 201

{ 150 }

This function prevents rapid shutdown of the FI according to the load. With the pulse switch-off
enabled, the output current is limited to the set value. This limitation is implemented by brief
switching off of individual output stage transistors, the actual output frequency remains
unchanged.

10...200% = Limit value related to the FI current rating

201 =

The function is so to speak switched off and the FI delivers the maximum possible
current. However, at the current limit the pulse switch off can still be active.

NOTE:

The value set here can be undershot with a smaller value in P536.

For smaller output frequencies (<4.5Hz) or higher pulse frequencies (>6kHz or
8kHz, P504) the pulse switch-off by the power reduction (see Section 8.3) can be
undershot.

NOTE:

If the pulse switch-off is disabled (P537=201) and a high pulse frequency is
selected in parameter P504, the FI automatically reduces the pulse frequency
when the power limit is reached. If the load on the FI is again reduced, the pulse
frequency increases to the original value again.

P539

Check output voltage

(Check output voltage)

S

P

0 ... 3

{ 0 }

This protective function monitors the output current at the U-V-W terminals and checks for
plausibility. In cases of error, the error message E016 is output.

0 = Disabled: Monitoring is not active.

1 = Only motor phase, "Only motor phase error": The output current is measured and

checked for symmetry. If an imbalance is present, the FI switches off and outputs the
error message E016.

2 = Only magnetisation, "Only magnetisation monitoring": At the moment the FI is

switched on, the level of the excitation current (field current) is checked. If insufficient
excitation current is present, the FI switches off with the error message E016. A motor
brake is not released in this phase.

3 = Motor phas + magnet., "Monitoring of motor phases + magnetisation": as 1 and 2

combined.

NOTE:

This function can also be used as an additional protective function for lifting
applications, but is not permissible on its own as protection for persons.