8 setpoint converter, sk cu4-rel, Setpoint converter, sk cu4-rel – NORD Drivesystems BU0200 User Manual

Page 97

Advertising
background image

SK 200E Manual for frequency inverters

96

Subject to technical alterations

BU 0200 GB-4411

3.4.8

Setpoint converter, SK CU4-REL

The analog inputs of SK 2x0 E series frequency inverters and the optional mains units SK xU4-24V can only
process unipolar setpoin

t values referenced to GND (0/2 … 10V; 0/4 … 20mA). If a bipolar setpoint

(-

10V … + 10V)) is available, this must be converted to a 0 … 10V signal by means of an SK CU4-REL

setpoint converter.

Two coupling relays are integrated into the module. These are controlled via the digital outputs of the
frequency inverter and can be used as openers or closers according to their connection.

+24V control voltage

2x Analog inputs (-

10 … +10V)

2x digital inputs

2x Analog outputs (0 … 10V)

2x Relay outputs (each configured as changeovers)

Max. permissible continuous relay current 100mA
(

≤30VDC)

incl. cable set

The terminal bar of the customer unit SK CU4-PBR-

… is divided into two potential levels (potential

separation max. 50VDC). On delivery, these are connected together with a plug-in jumper.

The bipolar analog signals must be connected to input terminals 114 or 116. Via the analog outputs
(Terminal 117 or 118) the signals which are transformed to 0...10V can be accessed and transferred to the
frequency inverter for further processing. In order to ensure the function of the analog signal converter, the
10V

DC

reference voltage of the frequency inverter must be wired to the reference potential of the setpoint

source(s) of the SK CU4-REL

Up to 2 digital signals can be transferred to the coupling relays from the frequency inverter. Regardless of
the wiring, both relays each provide the possibility of accessing an opening (NC) or a closing (NO) signal.

The module must be supplied with 24V

DC

.

To separate the two potential levels, the jumper (at the start of the series terminal) must be pulled out.

R21

R22

R24

R11

R12

R

14

40

C2

C1

118

117

116

114

111

112

44

Relay 1

Connection of the 24V power
supply from the SK 2x0E

AOUT connection of the
SK CU4 to AIN of the SK 2x0E

24V

AGND / 0V

Connection

to

the

terminal

bar

of the SK CU4-REL-

10V REF.

DI1

AOUT1

R11

/

R14

=

NO

R11 / R12 = NC

SK CU4-

SK 2x0E-

Digital control IN of the SK CU4 via
DO from the SK 2x0E

AIN1

Connection for bipolar analog
signals

Potential level:

Analog

Potential level:

Digital / Relay

11

12*

44

1

1

6

14

40

3

AIN2

AOUT2

DI2

Relay 2

R21

/

R24

=

NO

R21 / R22 = NC

* Terminal 12 or Terminal 40

GND / 0V

Similar to illustration