SK 200E Manual for frequency inverters

112

Subject to technical alterations

BU 0200 GB-4411

Details of the control connections

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

1

24V

2

24V supply

(module, field and system
bus level)

24VDC ±20%

≈ 900mA
protected against reverse
polarity


Max. permissible current
load: 500mA

Connection for module supply
voltage and 24V source for the
digital inputs (DIN1 to DIN4)

-

3

PB B

(incoming)

4

(outgoing)

PBR B
Bus + (red wire)

RxD/TxD-N

RS485 transfer
technology

The use of a twisted, shielded two-
wire cable / Profibus cable type A
is strongly recommended

-

5

PB A

(incoming)

6

(outgoing)

PBR A
Bus - (green wire)

RxD/TxD-P

-

7

0V-B

8

Data ground Bus

Reference potential for
internal Profibus voltage
supply

-

9

RTS

Ready to send

-

10

5V B

5V bus supply
voltage

internal Profibus voltage
supply

Note: Should not be used

externally!

-

Potential separation

11

24V

12

13

24V supply

(Module, field and system
bus level)

As for terminal 1

However, max.
permissible current load:
3A

Connection for module supply
voltage and 24V source for the
digital inputs (DIN1 to DIN4)

-

15

GND

17

18

GND
Reference potential
for digital signals

-

14

Sys+

System bus
data cable +

System bus
interface

-

16

Sys-

System bus
data cable -

-

19

DIN1

Digital input 1

(I/O Profibus DIN1)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1ms

Inputs compliant with
EN 61131-2,

Type 1

Each digital input has a reaction
time of 1ms

P174

20

DIN3

Digital input 3

(I/O Profibus DIN3)

P174