SK 200E Manual for frequency inverters

268

Subject to technical alterations

BU 0200 GB-4411

Display in the
SimpleBox

Warning

Text in the Parameter Box

Cause

Remedy

Group

Details in
P700 [-02]

C004

4.1

Overcurrent measurem

"Overcurrent from overcurrent
measurement"

Warning: Pulse switch-off is active

The limiting value for the activation of the pulse switch-off
(P537) has been reached (only possible if P112 and P536
are switched off)

FI is overloaded

Check motor data (P201 … P209)

C012

12.1

Limit moto /Customer
"Motor switch-off limit"

Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.

Reduce load on motor.

Set a higher value in (P534 [-01]).

12.2

Limit gen

"Generator switch-off limit"

Warning: 80% of the generator switch-off limit (P534 [-02])
has been exceeded.

Reduce load on motor.

Set a higher value in (P534 [-02]).

12.3

Torque limit

Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12

12.4

Current limit

Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14

12.5

Load limit

Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).

Adjust load.

Change limit values ((P525) ... (P527)).

Increase delay time (P528).