Electrical data 1~230V

Size 1

Size 2

(only SK 2x5E...)

Device type:

SK 2xxE… -250-123-A

-370-123-A

-550-123-A

-750-123-A

-111-123-A

Nominal motor power

(4-pole standard motor)

230V

0.25 kW

0.37 kW

0.55 kW

0.75 kW

1.1 kW

240V

1

/

3

hp

½ hp

¾ hp

1 hp

1½ hp

In

p

u

t

Mains voltage

1~ 230V

1 AC 200 ... 240V,

10%, 47 ... 63 Hz

Typical input current
at 230V

1~ rms

3.9 A

5.8 A

7.3 A

10.2 A

14.7 A

1~ FLA

3.9 A

5.8 A

7.3 A

10.1 A

14.6 A

Rec. mains fuse

1 AC

slow-acting [A]

10 A

10 A

16 A

16 A

16 A

Permissible
mains fuses (UL)

RK5 or faster

fuses,

min 230V

10 A

10 A

10 A

30 A

30 A

Bussmann

FRS-R-10

FRS-R-10

FRS-R-10

FRS-R-30

FRS-R-30

Circuit breaker*

min. 230V

10 A

10 A

10 A

25 A

25 A

O

u

tp

u

t

Output voltage

3~ 230V

3 AC 0 - Mains voltage

Nominal output
current at 230V

rms

1.7 A

2.2 A

2.9 A

4.0 A

5.5 A

Motor

Assembly**

1.7 A

2.2 A

2.6 A

4.0 A

5.5 A

Wall-mounted**

1.7 A

2.2 A

2.9 A

4.0 A

4.4 A

Min. braking resistor

75

75

75

75

75

Recommended braking
resistor

Section 2.3

100

100

100

100

100

Motor-mounted (ventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.25kW / 1.6A

0.25kW / 1.7A

0.25kW / 1.7A

0.25kW / 1.8A

0.37kW / 2.0A

0.37kW / 2.2A

0.37kW / 2.5A

0.55kW / 2.8A

0.55kW / 2.9A

0.55kW / 3.4A

0.55kW / 3.7A

0.75kW 4.0A

0.75kW 4.3A

0.75kW 4.8A

1.10kW / 5.4A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

49°C

50°C

50°C

33°C

45°C

40°C

36°C

45°C

40°C

35°C

45°C

40°C

29°C

40°C

35°C

Wall mounting (ventilated / unventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

S1-30°C

0.25kW / 1.5A

0.25kW / 1.7A

0.25kW / 1.7A

0.37kW / 2.2A

0.37kW / 2.2A

0.37kW / 2.2A

0.37kW / 2.7A

0.55kW / 2.9A

0.55kW / 2.9A

0.75kW / 4.0A

0.75kW / 4.0A

0.75kW / 4.0A

0.75kW / 4.3A

0.75kW / 4.8A

1.10kW / 5.3A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

44°C

50°C

45°C

50°C

50°C

50°C

42°C

45°C

45°C

50°C

50°C

50°C

27°C

40°C

35°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)

Advertising