NORD Drivesystems BU0200 User Manual
Page 155

SK 200E Manual for frequency inverters
154
Subject to technical alterations
BU 0200 GB-4411
5.2.2.4
Details of the potentiometers P1 and P2 (SK 2x0E S 4 and SK 2x5E)
The setpoint can be adjusted to a fixed value with the integrated potentiometer P1. Adjustment of the start-
up and braking ramps can be made via potentiometer P2.
Potentiometer
P1
(continuous)
P2
(stepped)
0% P102/103
P105
-
-
-
10%
0.2s
10Hz
1 P102/103
P104
20%
0.3s
20Hz
2
0.2s
2Hz
30%
0.5s
30Hz
3
0.3s
5Hz
40%
0.7s
40Hz
4
0.5s
10Hz
50%
1.0s
50Hz
5
0.7s
15Hz
60%
2.0s
60Hz
6
1.0s
20Hz
70%
3.0s
70Hz
7
2.0s
25Hz
80%
5.0s
80Hz
8
3.0s
30Hz
90%
7.0s
90Hz
9
5.0s
35Hz
100%
10.0s
100Hz
10
7.0s
40Hz
The function of P1 and P2 depends on DIP 4/5. The meaning
changes according to the setting.
As standard, P1 sets the setpoint value of 0-100% and P2 sets the
ramp from 0.2-7sec.
Potentiometer
P2
P1