9.6 Operation with FI circuit breakers

With SK 2xxE frequency inverters (except 115V devices), leakage currents of > 40mA are to be expected if
the mains filter is active. If possible, an FI circuit breaker for the protection of personnel should not be used.

If the frequency inverter is to be used with an FI circuit breaker for the protection of personnel, the leakage
currents to earth must be reduced to 10 - 20 mA by means of jumpers. However, with "operation on an IT
network" the FI loses its specified degree of interference protection.

Further details can be found in Section 2.7.5.

9.7 System bus

SK 2xxE series frequency inverters and components communicate with each other via the system bus. This
bus system is a CAN bus with a Canopen protocol. Up to four frequency inverters and their associated
components (field bus module, absolute encoder, I/O modules etc.) can be connected to the system bus.
Integration of the components into the bus does not require any BUS-specific knowledge on the part of the
user.

It is only necessary to take care that the correct physical structure of the bus system and the correct
addressing of the participants are complied with.

The connection of the individual NORD components is described in this manual
(See Section 2.8, 3.4 and 3.5).

Physical structure

Standard

CAN

Bus length

20m with a wire cross section of 0.25mm² (AWG23)

Structure

preferably linear

Spur cables

possible, (max. 6m)

Termination resistors

120Ω, 250mW at both ends of a system bus

(with SK 2xxE-

… or SK xU4-… via DIP switches)

Baud rate

250kBaud - preset

SYSTEM BUS

Configuration Example

1. FI

2. FI

3. FI

4. FI

1. I/O

Extension

8. I/O

Extension

Field Bus

Option

additional participants
(I/O extensions, CANopen encoder

Note:
Terminal77 = System bus + (CAN H)
Terminal78 = System bus - (CAN L)
Terminal numbers may differ