6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

205

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P434

[-01]

[-02]

Digital output function

(Function of digital outputs)

0 ... 39

{ 7 }

[-01] =

Digital output 1, Digital output 1 of the frequency inverter

[-02] =

Digital output 2, Digital output 2 of the frequency inverter (only SK 2x0E)

Control terminals 1/40 (Section 2.8.2): The settings 3 to 5 and 11 work with 10% hysteresis,
i.e. the relay contact closes (function 11 does not deliver) on reaching the limiting value 24V and
switches this off again if a 10% lower value is undershot (function 11 on again).

This behaviour can be inverted with a negative value in P435.

Setting / Function

Output ...

for limiting value

or function

(see also P435)

0 = No function

Low

1 = External brake, to control an external 24V brake relay (max. 200mA).

The relay switches at a programmed absolute minimum frequency
(P505).

For typical brakes a setpoint delay of 0.2-0.3sec should be
programmed (see also P107/P114).

A typical motor brake (105-180-205V) can be connected directly via
the control terminals 79 MB+/80 MB- (Section 2.8.2).

High

2 = Inverter is working, the output indicates voltage at the FI output

(U - V - W)

.

High

3 = Current limit, based on the setting of the motor rated current in (P203).

This value can be adjusted with the standardisation (P435).

High

4 = Torque current limit, based on motor data settings in P203 and P206.

Signals a corresponding torque load on the motor. This value can be
adjusted with the standardisation (P435).

High

5 = Frequency limit, based on motor nominal frequency setting in P201.

This value can be adjusted with the standardisation (P435).

High

6 = Level with setpoint (Setpoint reached), indicates that the FI has

completed the frequency increase or decrease. Setpoint frequency =
actual frequency! From a difference of 1 Hz  Setpoint value not
achieved

– signal Low.

High

7 = Fault, general error message, error is active or not yet acknowledged.

Error

– Low (Ready – High)

Low

8 = Warning: general warning, a limit value was reached that could lead to

a later shutdown of the FI.

Low

9 = Overcurrent warning: At least 130% of the nominal FI current was

supplied for 30 seconds.

Low

10 = Overtemp. Warn. Motor, "Motor overtemperature warning": The motor

temperature is evaluated.  Motor is too hot. Warning occurs
immediately, overheating switch-off after 2 seconds.

Low

11 = Torque curr. lim. active, "Torque current limit / Current limit active

warning": The limiting value in P112 or P536 has been reached. A
negative value in P435 inverts the reaction. Hysteresis = 10%.

Low

12 = Value of P541, "Value of P541 - external control": The output can be

controlled with parameter P541 (Bit 0) independent of the actual
operating status of the FI.

High

13 = Torq curr limit gen,

"Generator torque limit active":

Limit value in P112 has been reached in the generator range.
Hysteresis = 10%.

High