3 motor data / characteristic curve parameters – NORD Drivesystems BU0200 User Manual

Page 183

Advertising
background image

SK 200E Manual for frequency inverters

182

Subject to technical alterations

BU 0200 GB-4411

6.1.3

Motor data / characteristic curve parameters

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P200

Motor list

(Motor list)

P

0 ... 45

{ 0 }

The factory settings for the motor data can be edited with this parameter. The factory setting in
parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.

By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a
4-pole DS standard motor.

0 = No change "No change of data"

1 = No motor: In this setting, the FI operates without current control, slip compensation and

pre-magnetising time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. The following motor data is set here:
50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos

=0.90 / star / R

S

0.01

/ I

EMPTY

6.5A

2 = 0.25 kW 230V

3 = 0.33 HP 230V

4 = 0.25 kW 400V

5 = 0.33 HP 460V

6 = 0.37 kW 230V

7 = 0.50 HP 230V

8 = 0.37 kW 400V

9 = 0.50 HP 460V

10 = 0.55 kW 230V

11 = 0.75 HP 230V

12 = 0.55 kW 400V

13 = 0.75 HP 460V

14 = 0.75 kW 230V

15 = 1.0 HP 230V

16 = 0.75 kW 400V

17 = 1.0 HP 460V

18 = 1.1 kW 230V

19 = 1.5 HP 230V

20 = 1.1 kW 400V

21 = 1.5 HP 460V

22 = 1.5 kW 230V

23 = 2.0 HP 230V

24 = 1.5 kW 400V

25 = 2.0 HP 460V

26 = 2.2 kW 230V

27 = 3.0 HP 230V

28 = 2.2 kW 400V

29 = 3.0 HP 460V

30 = 3.0 kW 230V

31 = 3.0 kW 400V

32 = 4.0 kW 230V

33 = 5.0 HP 230V

34 = 4.0 kW 400V

35 = 5.0 HP 460V

36 = 5.5 kW 230V

37 = 7.5 HP 230V

38 = 5.5 kW 400V

39 = 7.5 HP 460V

40 = 7.5 kW 230V

41 = 10 HP 230V

42 = 7.5 kW 400V

43 = 10 HP 460V

44 = 11.0 kW 400V

45 = 15.0 HP 460V

46 = 15.0 kW 400V

47 = 20.0 HP 460V

48 = 18.5 kW 400V

49 = 25.0 HP 460V

50 = 22.0 kW 400V

51 = 30.0 HP 460V

52 = 30.0 kW 400V

53 = 40.0 HP 460V

NOTE:

As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.

If DIP switch S1:7 (50/60Hz operation, Section 5.2.2.2) is switched over, the
appropriate nominal motor data according to the FI power rating are reloaded from
the P200 list.

P201

Nominal frequency

(Nominal motor frequency)

S

P

10.0 ... 400.0 Hz

{

}

The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.

P202

Nominal speed

(Nominal motor speed)

S

P

150 ... 24000 rpm

{

***

}

The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).

*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.