5 Commissioning

5.1 Factory settings

All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for
standard applications with 4 pole standard motors (same voltage and power). For use with motors with
other powers or number of poles, the data from the name plate of the motor must be input into the
parameters P201...P207 under the menu item >Motor data<.

NOTE:

All motor data can be pre-set using the parameter P200. After successful use of this
function, this parameter is reset to 0 = no change! The data is loaded automatically into
parameters P201...P209

– and can be compared again with the data on the motor name

plate.

3~ Mot
IEC 56
IM B3

cos

0,74

cos

0,74


IP55

Rot. KL 16

Th.Cl.F

EN60034

60 Hz

460 V Y

5,2 A

2,5 kW

1765 /min

1440 /min

P206

P201

P204

P203 P202

P200

9,0 /

5,2 A

50 Hz

2,2 kW

P207

P200 Motor list:
0 = no change

8 = 0.37 kW 400V

1 = no motor

9 = 0.50 HP 460V

2 = 0.25 kW 230V

10 = 0.55 kW 230V

3 = 0.33 HP 230V

11 = 0.75 HP 230V

4 = 0.25 kW 400V

12 = 0.55 kW 400V

5 = 0.33 HP 460V

13 = 0.75 HP 460V

6 = 0.37 kW 230V

14 = 0.75 kW 230V

7 = 0.50 HP 230V ....

230 /

400 V

/

Y

RECOMMENDATION: For the correct operation of the drive unit, it is necessary to input the motor data

according to the name plate as precisely as possible. In particular, an automatic
stator resistance measurement using parameter P220 is recommended.

In order to automatically determine the stator resistance, P220 = 1 must be set and
confirmed by pressing "OK". The value calculated for the line resistance
(dependent upon P207) will be saved in P208.

ATTENTION

After a default setting "Enable Left" or "Enable Right", the digital inputs DIN2 and DIN3 are
additionally assigned for the evaluation of an HTL incremental encoder. The encoder evaluation
function cannot be switched off. This means that with the use of an incremental encoder, it is
essential to set parameters (P420[-02]) and (P420[-03]) to "no function".

This can also be implemented with the inverter DIP switch (S1) (Section 5.2.2).

NOTE

It must be noted that DIP switch settings on the frequency inverter have priority over the
parameter settings.

In addition, the settings of the integrated potentiometers P1 and P2 must be taken into account.