3 table of possible warning messages, N 7.3), And 7.3 – NORD Drivesystems BU0200 User Manual

Page 268

Advertising
background image

7 Status messages

BU 0200 GB-4411

Subject to technical alterations

267

7.3 Table of possible warning messages

Display in the
SimpleBox

Warning

Text in the Parameter Box

Cause

Remedy

Group

Details in
P700 [-02]

C001

1.0

Inverter

overtemp

"Inverter overtemperature"
(inverter heat sink)

Warning from output stage module (static)

Reduce ambient temperature <50°C or <40°C (see also
Section 8 Technical data).

Check control cabinet ventilation

C002

2.0

Motor overtemp PTC
"Overtemperature of motor
PTC"

(from thermistor)

Warning from motor temperature sensor (triggering
threshold reached)

Reduce motor load

Increase motor speed

Use external motor fan

2.1

Motor

overtemp I²t

"Overtemperature of motor from
I²t"

(Only if I

2

t- motor (P535) is

programmed.)

Warning: Motor I

2

t monitoring (Attainment of 1.3x the rated

current for the period specified in (P535))

Reduce motor load

Increase motor speed

2.2

Ext. resistor temp

"Overtemperature of external
brake resistor"

Overtemperature via digital
input (

P420 […])={13}

Warning: Temperature monitor has triggered

Digital input is Low

C003

3.0

Overcurrent I²t lim

"Overcurrent I²t limit"

Warning: Rectifier I

2

t limit,

(e.g. output current > NFI current rating)
(Attainment of 1.3x the inverter current rating for a period of
60 s)

Continuous overload at inverter output

(Please also note P504)

3.1

Overcurrent, chopper

"Overcurrent, chopper I2t"

Warning: I

2

t limit for brake chopper has triggered

(Attainment of 1.3x the value for a period of 60s)
(Please also note P555, P556, P557)

Avoid overcurrent in braking resistance

3.5

Torque limit
"Torque current limit"

Warning: torque current limit reached (P112)

3.6

Current limit

Warning: current limit reached (P536)

Advertising