Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

21

0V

22

GND
Reference potential
for digital signals

As for terminal 15

Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN4)

-

23

24V

24

24V supply

(module, system bus level)

As for terminal 11

-

25

DIN2

Digital input 2

(I/O DeviceNet DIN2)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1ms

Each digital input has a reaction
time of 1ms

Inputs compliant with
EN 61131-2,

Type 1

P174

26

DIN4

Digital input 4

(I/O DeviceNet DIN4)

P174

27

0V

28

GND
Reference potential
for digital signals

As for terminal 15

Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN4)

-

29

24V

30

24V supply

(module, system bus level)

As for terminal 11

-

Potential separation

31

24V 2

24V supply
of digital outputs

24VDC -/+20%

Up to 1A, according to
load

reverse polarity protected

Supply voltage connection for
digital outputs (DO1 and DO2)

If necessary, bridge to

24V

terminal

-

32

0V 2

GND 2
Reference potential
for digital outputs

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

33

DO1

Digital output 1

(I/O DeviceNet DO1)

Low = 0V
High: 24V

Rated current: 500mA
each

The digital outputs should be used
with a separate 24V supply.

P175

34

DO2

Digital output 2

(I/O DeviceNet DO2)

P175

35

0V 2

36

GND
Reference potential
for digital signals

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

Detailed information about operation via DeviceNet can be found in the relevant supplementary manual