2 motor cable (u, v, w, earth), 3 brake resistor connection (-b, +b) – NORD Drivesystems BU0200 User Manual

Page 43

Advertising
background image

SK 200E Manual for frequency inverters

42

Subject to technical alterations

BU 0200 GB-4411

2.7.2

Motor cable (U, V, W, earth)

The motor cable may have a total length of up to 100m if this is a standard cable. If a screened motor
cable is used, or if the cable is laid in a well earthed metal conduit, the total length should not exceed
20m
. In order to comply with interference suppression class C2, a total length of 5m must not be
exceeded.

Note:

Please also note Section 9.4 EMC limit
value classes.

Note:

For multiple motor use the total cable length
consists of the sum of the individual cable
lengths.

Note:

The motor cable must not be switched as
long as the inverter is providing power to the
motor. (The inverter must be on "Standby"
or "Starting Disabled")

Connection cross-section:

Size 1 … 3:

0.5 ... 6mm

2

rigid/flexible cable AWG 20-10

Size 4:

0.5 ... 16mm

2

rigid/ flexible cable AWG 20-6

Tightening torque:

1.2 ... 1.5Nm

2.7.3

Brake resistor connection (-B, +B)

Terminals +B/ -B are intended for the connection of a suitable braking resistor. The connection should be as
short as possible.

Note:

The large amount of heat produced by the
brake resistor must be taken into account.

Connection cross-section:

Size 1 … 3:

0.5 ... 6mm

2

rigid/ flexible cable AWG 20-10

Size 4:

0.5 ... 16mm

2

rigid/ flexible cable AWG 20-6

Tightening torque:

1.2 ... 1.5Nm

PE

Motor

Advertising