7 Status messages

BU 0200 GB-4411

Subject to technical alterations

261

Display in the
SimpleBox

Error

Text in the Parameter Box

Cause

Remedy

Group

Details in
P700[-01] /
P701

E003

3.0

Overcurrent I²t lim

"Overcurrent I²t limit"

Rectifier I

2

t limit has triggered,

e.g. > 1.5 x I

n

for 60s

(Please also note P504)

Continuous overload at inverter output

3.1

Overcurrent, chopper

"Overcurrent, chopper I2t"

I

2

t limit for brake chopper has triggered

(Attainment of 1.5x the value for a period of 60s)
(Please also note P555, P556, P557)

Avoid overcurrent in braking resistance

3.2

Overcurrent IGBT
monitoring 125%

De-rating (power reduction)

125% overcurrent for 50ms

Brake chopper current too high

for fan drives: enable flying start circuit
(P520)

See also
Section 9.5

3.3

Overcurrent IGBT fast
monitoring 150%

De-rating (power reduction)

150% overcurrent

Brake chopper current too high

E004

4.0

Overcurrent module

Error signal from module (short duration)

Short-circuit or earthing fault at FI output

Motor cable is too long

Use external output choke

Brake resistor faulty or resistance too low (Section 8)

4.1

Overcurrent measurem

"Overcurrent from overcurrent
measurement"

P537 (pulse current switch-off) was reached 3x within 50ms
(only possible if P112 and P536 are disabled)

FI is overloaded
(Drive unit sluggish, too small,
Ramps (P102/P103) to steep

→ Increase ramp time)

Check motor data (P201 … P209)

E005

5.0

Overvoltage, Ud

Frequency inverter link circuit voltage is too high

Reduce energy return by means of a braking resistance

Extend braking time (P103)

If necessary, set switch-off mode (P108) with delay (not for
lifting equipment)

Extend quick stop time (P426)

5.1

Overvoltage mains

Mains voltage is too high

Please check 380V-

20% … 480V+10%

or 200 … 240V

10%

E006

---

reserved

E007

---

reserved