SK 200E Manual for frequency inverters

64

Subject to technical alterations

BU 0200 GB-4411

2.10.4

Commissioning information

For Zone 22 the cable glands must at least comply with protection class IP 55. Unused openings must be
closed with blank screw caps suitable for ATEX Zone 22 3D (minimum protection class IP 55).

The motors are protected against overheating by means of the frequency inverter. This is carried out by the
evaluation of the motor PTC by the frequency inverter. In order to ensure this function, the PTC must be
connected to the intended input (Terminal 38/39 control terminal plug connector). In addition, care must be
taken that a NORD motor from the motor list (P200) is set. If a standard 4-pole NORD motor or a motor from
a different manufacturer is not used, the data for the motor parameters ((P201) to (P208)) must be adjusted
to those on the motor name plate. In addition, the frequency inverter must be parameterised so that the
motor can be operated with a maximum speed of 3000

P

1

P

/

B

min

B

. For a four-pole motor, the "maximum

freque

ncy" must be set to a value which is smaller or equal to 100Hz ((P105) ≤ 100). Here the maximum

permissible output speed of the gear unit must be observed. In addition, the monitoring "I²t-Motor"
(Parameter (P535) / (P533)) must be switched on and the pulse frequency set to between 4 kHz and 6 kHz.

Overview of the necessary parameter settings:

Parameter

Setting value

Factory setting

Description

P105
Maximum
frequency

≤ 100 Hz

[50]

This value relates to a 4-pole motor. On principle,
the value must only be so large that a motor
speed of 3000 rpm is not exceeded.

P200
Motor list

Select the appropriate
motor power

[0]

If a 4-pole NORD motor is used, the preset motor
data can be called up.

P201

– P208

Motor data

Data according to name
plate

[xxx]

If a 4-pole NORD motor is not used, the motor
data on the name plate must be entered here.

P218
Degree of
modulation

≥ 100%

[100]

Determines the maximum possible output voltage

P504

Pulse frequency

4kHz … 6kHz

[6]

For pulse frequencies above 6kHz a reduction of
the maximum torque is necessary.

P533

Factor I2t motor

< 100%

[100]

A reduction in torque can be taken into account
with values less than 100 in the I²t monitoring.

P535

I²t motor

According to motor and
ventilation

[0]

The I²t- monitoring of the motor must be switched
on. The set values depend on the type of
ventilation and the motor used. See
Planning Guideline No.: 605 2101