5 Commissioning

BU 0200 GB-4411

Subject to technical alterations

153

5.2.2.3

DIP switch configuration, analog input (only SK 2x0E)

The analog inputs in the SK 2x0E are suitable for current and voltage set-
points. For correct processing of current setpoints (0-20mA / 4-20mA) the
relevant DIP switch must be set for current signals ("ON").

Adjustment (to fail-safe signals in case of cable breaks (2-10V / 4-20mA) is
made via parameters (P402) and (P403).

Access to DIP switches

SK 2x0E

Access

Detail

S 1 … 3

… from outside, middle
diagnostic opening

Size 4

... from inside