5 Commissioning
BU 0200 GB-4411
Subject to technical alterations
153
5.2.2.3
DIP switch configuration, analog input (only SK 2x0E)
The analog inputs in the SK 2x0E are suitable for current and voltage set-
points. For correct processing of current setpoints (0-20mA / 4-20mA) the
relevant DIP switch must be set for current signals ("ON").
Adjustment (to fail-safe signals in case of cable breaks (2-10V / 4-20mA) is
made via parameters (P402) and (P403).
Access to DIP switches
SK 2x0E
Access
Detail
S 1 … 3
… from outside, middle
diagnostic opening
Size 4
... from inside