Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the DIP
switch on the I/O extension module. In this case, additional adjustment of parameters (P402)
and (P403) must not be carried out.

P400 ... P403

Output
frequency

P104

z.B. 0,0 V 2,5 V 5,0 V 10,0 V

P105

positive

P402

P403

Setpoint
voltage

Output
frequency

P104

z.B. 0,0 V 2,5 V 5,0 V 10,0 V

P105

positive

negative

P402

P403

Setpoint
voltage

P404

[-01]

[-02]

Analog input filter

(Analog input filter)

SK 2x0E

1 ... 400 ms

{ all 100 }

Adjustable digital low-pass filter for the analog signal. Interference peaks are hidden, the
reaction time is extended.

[-01] =

Analog input 1

[-02] =

Analog input 2

P410

Min. freq. a-in 1/2

(Minimum frequency a-in 1/2
(auxiliary setpoint value))

P

-400.0 ... 400.0 Hz

{ 0.0 }

The minimum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies which are additionally supplied for further functions in the
FI:

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

PI process controller

PI controller

Multiplication

P411

Max. freq. a-in 1/2

(Maximum frequency a-in 1/2
(auxiliary setpoint value))

P

-400.0 ... 400.0 Hz

{ 50.0 }

The maximum frequency that can act on the setpoint via the auxiliary setpoints.

Auxiliary setpoints are all frequencies which are additionally delivered for further functions in the
FI:

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

PI process controller

PI controller

Multiplication