Mains unit, SK TU4-24V-

… (only SK 2x5E)

The mains unit is used to produce the 24V control voltage for SK 2x5E frequency inverters from the
available mains voltage (115V/230V/380V/500V). With this, a separate external 24V control voltage is not
necessary.

An analog output is also available for the connection of a potentiometer.

Mains unit for 100-240V, SK TU4-24V-123-B

Mains unit for 380-500V, SK TU4-24V-140-B

+24V- output voltage

1x analog input (e.g. potentiometer)

1x impulse output

Status LED = 24V

Max. permissible continuous current: 420mA

The Mains unit SK TU4-24V-

…can only be used in combination with an SK TI4-TU-NET adapter unit.

Details of the control connection are described in the Section for the Adapter Unit (Section 3.5.1.2)

A connection and parameterisation example is described in Section 3.4.1.

To process current setpoint values (0(4)-

20mA), the enclosed bag contains a 500Ω resistor, for connection

between terminals 12 and 14. Matching of the relevant input of the frequency inverter is made via parameter
(P420).

Setpoint

Parameter [Array]

Setting

0 … 20mA P420 [-02] or [-03] {26}
4 … 20mA P420 [-02] or [-03] {27}

NOTE

The use of SK CU4-24V-

… / SK TU4-24V-… on the SK 2x0E is not permissible!

A mains unit is integrated into the SK 2x0E inverter models, so that no external 24V DC is
required.