4 parameterbox error messages, P1305, P1306 – NORD Drivesystems BU0200 User Manual

Page 146: P1307, P1308

Advertising
background image

4 Display and control

BU 0200 GB-4411

Subject to technical alterations

145

Parameter

Setting value / Description / Note

P1305

Set password

The user can set up a password in this parameter.

If a value other than 0 has been entered in this parameter (default setting), then the settings
of the ParameterBox or the parameters of the connected inverter cannot be altered.

P1306

Box password

If the >Password< function is to be reset, the password selected in the >Set Password<
parameter must be entered here. If the correct password is selected, all of the
ParameterBox functions and the parameters of the connected frequency inverter can be
used again.

NOTE: With the master-

password „65‟ the current password is displayed and can be

confirmed with the OK key.

P1307

Reset Box parameter

With this parameter the ParameterBox can be reset to the default setting. All ParameterBox
settings and the data in the storage media will be deleted.

P1308

Software version

Displays the software version of the ParameterBox. In case of service enquiries by
telephone, please have this at hand.

4.2.4

ParameterBox error messages

Display

Error

Cause

Remedy

Communication error

200

INCORRECT PARAMETER NUMBER

These error messages are due to EMC interferences or differing software

versions of the participants.

 Check the software version of the ParameterBox and that of the

connected frequency inverter.

 Check the cabling of all components, regarding possible EMC

interference

 Plug-in EEPROM on the frequency inverter (memory module) not

recognised (Error: 201)

→Check for correct connection

201

PARAMETER VALUE CANNOT BE
CHANGED

202

PARAMETER OUTSIDE VALUE
RANGE

203

FAULTY SUB INDEX

204

NO ARRAY PARAMETERS

205

WRONG PARAMETER TYPE

206

INCORRECT RESPONSE
RECOGNITION USS INTERFACE

207

USS INTERFACE
CHECKSUM ERROR (RS485)

Communication between frequency inverter and ParameterBox is faulty

(EMC), safe operation cannot be guaranteed.

 Check the connection to the frequency inverter. Use a shielded cable

between the devices. Route the BUS leads separately from the motor
cables.

208

FAULTY STATUS RECOGNITION

USS INTERFACE (RS485)

Communication between frequency inverter and ParameterBox is faulty

(EMC), safe operation cannot be guaranteed.

 Check the connection to the frequency inverter. Use a shielded cable

between the devices. Route the BUS leads separately from the motor
cables.