6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

191

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter set

P326

Ratio encoder

(Encoder transformation ratio)

S

0.01 ... 100.00

{ 1.00 }

If the incremental encoder is not mounted directly onto the motor shaft, then the respectively
correct transformation ratio of motor speed to encoder speed must be set.

speed

Encoder

speed

Motor

P326

Only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor speed control)

P327

Speed slip error

(Speed slip error, speed control)

S

P

0 ... 3000 rpm

{ 0 }

The limit value for a permitted maximum slip error can be set. If this value is reached, the FI
switches off and indicates error E013.1.

0 = OFF

Only when P325 = 0, therefore in Servo mode (motor speed control)

P328

Speed slip delay

(Speed slip error delay)

S

P

0.0 ... 10.0 s

{ 0.0 }

In case the permissible slip error defined in (P327) is exceeded, the display of the error
message E013.1 is suppressed within the limits which can be set here.

0 = OFF