5 other options, 3 maximum output voltage and torque reduction – NORD Drivesystems BU0200 User Manual

Page 64

Advertising
background image

2 Assembly and installation

BU 0200 GB-4411

Subject to technical alterations

63

2.10.2.5 Other options

M12 sockets and plugs for installation in the terminal box of the basic device or in technology units may only
be used of they are approved for use in ATEX Zone 22 3D.

Name

Part Number

Approved for
ATEX Zone 22 3D

Not approved for
ATEX Zone 22 3D

SK TIE4-WMK-1

275274000

x

SK TIE4-WMK-2

275274001

x

SK TIE4-WMK-TU

275274002

x

SK TIE4-HAN10E

275274100

x

SK TIE4-HANQ5

275274110

x

SK TIE4-SWITCH

275274610

x

SK TIE4-M12-M16

275274510

x

SK TIE4-M12-PBR

275274500

x

SK TIE4-M12-CAO

275274501

x

SK TIE4-M12-ASI

275274502

x

SK TIE4-M12-ASI-AUX

275274513

x

SK TIE4-M12-INI

275274503

x

SK TIE4-M12-ANA

275274508

x

SK TIE4-M12-SYSM

275274505

x

SK TIE4-M12-SYSS

275274506

x

SK TIE4-M12-POW

275274507

x

SK TIE4-M12-SH

275274509

x

SK TIE4-M12-HTL

275274512

x

2.10.3

Maximum output voltage and torque reduction

As the maximum output voltage depends on the pulse frequency to be set, in some cases the
torque which is stated in Planning Guideline 605 2101 must be reduced for values above the rated pulse
frequency of 6 kHz.

For F

pulse

> 6kHz:

T

reduction

[%] = 1% * (F

pulse

– 6kHz)

Therefore the maximum torque must be reduced by 1% for each kHz pulse frequency above 6kHz. The
torque limitation must be taken into account on reaching the break frequency. The same applies for the
degree of modulation (P218). With the factory setting of 100%, in the field reduction range a torque
reduction must be taken into account:

For P218 > 100%:

T

reduction

[%] = 1% * (105

– P218)

Above a value of 105%, no reduction needs to be taken into account. However, with values above 105% no
increase in torque above that of the Planning Guideline will be achieved. Under certain circumstances,
degrees of modulation > 100% may lead to oscillations and motor vibration due to increased harmonics.

ATTENTION

At pulse frequencies above 6 kHz (400/500V devices) or 8 kHz (230V) devices, the
reduction in power must be taken into account for the design of the drive unit.

If parameter (P218) is set to < 105%, the derating of the degree of modulation
must be taken into account in the field reduction range.