3.4.3.2

Configuration

The configuration of the system bus settings and the functions of the analog inputs and outputs is made via
a 12-part DIP switch element. Both analog inputs are differential inputs. The input voltage is simultaneously
measured in a unipolar and bipolar manner. The evaluation is unipolar or bipolar, according to the DIP
switch setting, with or without offset, as a current or voltage input.

If the module is configured for fail-safe signals in case of cable breaks (

2…10V / 4 .. 20mA), with signal lev-

els < 1V / < 2mA the frequency inverter switches to the state "Start disabled" (See also P700 [-03]). This
monitoring function is always active, even if the analog inputs are parameterised to "No function".

Range

Function

DIP switch

meaning

DIP switch

combinations

Signal

allocation

(DIP No.)

BIT2

BIT1

BIT0

C

o

n

figu

ra

tion

o

f

a

n

a

log

I

Os

Mode

Second - IOE

2nd IOE Mode

(12)

0

1

first

SK-

…-IOE on FI

second SK-

…-IOE on FI

Analog output

AOUT

Aout Mode Bit 1

(11)

0

0

1

0

0

1

0

1

0 … 10V

2 … 10V

0 … 20mA

4 … 20mA

Aout Mode Bit 0

(10)

Analog input AIN2

Ain2 Mode Bit 2

(09)

0

0

0

1

1

0

0

1

0

0

0

1

0

0

1

0 … 10V
2 … 10V

-

10 … 10V

0 … 20mA
4 … 20mA

Ain2 Mode Bit 1

(08)

Ain2 Mode Bit 0

(07)

Analog input AIN1

Ain1 Mode Bit 2

(06)

0

0

0

1

1

0

0

1

0

0

0

1

0

0

1

0 … 10V

2

… 10V

-

10 … 10V

0 … 20mA
4 … 20mA

Ain1 Mode Bit 1

(05)

Ain1 Mode Bit 0

(04)

B

u

s

-

C

o

n

figu

ra

tion

Addressing

System bus

S-Bus Addr. Bit 1

(03)

0

0

1

1

0

1

0

1

Address 20 (for FI0 Addr. 32)*

Address 21 (for FI1 Addr. 34)*

Address 22 (for FI2 Addr. 36)*

Address 23 (for FI3 Addr. 38)*

S-Bus Addr. Bit 0

(02)

System bus

termination resistor

S-Bus term.

(01)

0

1

not set

set

*for DIP12 = ON: Address 10 … 13 instead of 20 … 23

NOTE

Up to software version V1.0 R1 of the I/O extension the setpoint value of the analog output
could be inverted via DIP switch 12:

DIP12 setting "OFF":

100% setpoint = 10V

0% setpoint = 0V

DIP12 setting "ON":

100% setpoint = 0V

0% setpoint = 10V

With newer versions, this setting is made in parameter (P163) "Inversion AOut".

NOTE

The setting of the DIP switches is only read out during the initialisation phase. Changes
made while running are therefore not taken into account.

The side of the DIP switch element corresponding to "ON" should be checked (see label on
the DIP switch element) as for process reasons, this may vary during the manufacture of
the module.

1

....

12

Advertising